JSM Micro IN32B Universal Interface is ideal for residence owners who want to replace their existing emergency call system, without replacing all the call devices. These will then be connected to our Universal Interface which, in turn, will communicate with VIGILANCE Central Controller (WSX1) to handle emergency calls.

 

The table bellow compares the limits and possibilities of a system using this interface versus a full VIGILANCE system.

 

 

 

 

  Systeme with IN32B Interface   VIGILANCE System
       
CALL DEVICES All swith type (on/off) call devices   JSM Micro Enhanced Call Devices
       
CALL DEVICE INTERFACE IN32B Universal Interface   RTU-8 Enhanced Controle Module
       

CENTAL CONTROLLER

WSX1

 

WSX1

       
PRIORITY CALL LEVELS One   Multiple
       
CORRIDOR LAMPS on/off   Enhanced Support (flashing, colors)
       
CALL DEVICE SUPERVISION Optionnal   Included
       
CALL CONFIRMATION Basic   Enhanced
       
CALL DEVICE CONNECTION Welding   Plug In
       
REPORT GENERATION Basic JSM Report   Enhanced JSM Report

 

Technically, the IN32B interface monitors circuits or mechanical contacts such as lamps, relay contacts, switches, thermostats, alarms, etc. The status of the overseen devices is conveyed to a central controller (WSX1) which will react in accordance to its onboard firmware. For example, information can be stored, displayed on monitors, relayed to pagers, etc. The IN32B can detect steady or flashing signals on the same pin. Supervised mode is possible with steady signals only.

 

Features

  • Micro controller driven
  • Active/Passive protocols
  • RS485 networked
  • Field programmable, no PC required.
  • Accept dry contacts, N.O. or N.C.
  • Accept voltages 5-30 volts AC/DC
  • Accept supervised contacts
  • Active supervision mode, 10 seconds
  • Optically isolated inputs
  • Light grey cold rolled steel enclosure
  • 7.5 to 12 volts DC powered
  • Cage Clamp (no screw) connectors

Technical specifications

  • Power: 12 VDC, 140 ma (90 typical)
  • Programming: RS232 or manual (EEPROM holds configuration)
  • Network: RS485 (1 km shielded 1 pair cable or cat 5 cable)
  • Transmission: 9600 bauds, programmable buss protocol
  • Capacity: 1024 points (32 cards x 32 points)
  • Isolation: 5,000 volts RMS (nominal) by optical isolation
  • Inputs: 32, 2 commons (0-7, 8-31), 5 to 30 volts AC/DC 50-60Hz, 5000 ohms
  • Connections: WAGO “cage clamp” plug in type connectors
  • Enclosure: (W L H) 19.5cm x 9.5cm x 4cm (7.75po x 3.75po x 1.5po) metallic, painted.